Specifications

212 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
y Follow and Test
The output follows the programmed input one state and will retest the input state continually.
Input One Output
ON ON
OFF OFF
Test Action - If the output state is changed externally or is part of another programmable function the
programmable function will only restore the output state after 30 seconds has elapsed. This time is only
used if the programmable function was NOT responsible for the change in state.
y Not Follow and Test
Performs the same function as above however the output is inverted (NOT). This logic action is a test action,
consult the follow and test action for an explanation of the Test Function.
Input One Output
ON OFF
OFF ON
y Pulse On
The pulse on action will turn the output ON only when the input one has transitioned from an off to an on
state. The output will not be modified further from this state and will not be modified if it is turned OFF by
another function.
Input One Output
ON
y Not Pulse On
The not pulse on action will turn the output OFF only when the input one has transitioned from an off to an
on state. The output will not be modified further from this state and will not be modified if it is turned ON by
another function.
Input One Output
OFF
y Pulse Off
The pulse on action will turn the output ON only when the input one has transitioned from an ON to an OFF
state. The output will not be modified further from this state and will not be modified if it is turned OFF by
another function.
Input One Output
ON
y Not Pulse Off
The not pulse off action will turn the output OFF only when the input one has transitioned from an ON to an
OFF state. The output will not be modified further from this state and will not be modified if it is turned ON
by another function.
Input One Output
OFF
y OR Follow and Test