Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 205
Un-Secure Net
started...
If the screen displays a message that the network security process could not be disabled this will be due to a
network update process being operational. What for the update process to complete and then request the
network security disable again.
Cancel Module Update
In some cases it may be required to cancel an update of the modules. This can be done using the cancel
module update option. The cancel module update will prompt the user for the update type to cancel if it is
running an update or inform the user that there is nothing to cancel. To cancel a module update function select
[MENU, 4, 8, 1, 8] the following display explains the screen information and actions that are performed.
y Select the cancel update option from the network menu. The display will present a message with the
current update in process. If you want to continue and cancel the update process shown press the
[ENTER] key, to exit press the [MENU] key or any other key.
Offline update
cancel?
y Pressing the [ENTER] key the keypad will display the message below if the offline update has been
canceled.
Offline update
canceled....
The screen will then return to the menu item that was selected.
Reset Network Statistics
To reset the network statistics press the [FORCE] key while in any of the statistic display screens. The statistic
counters will not increment past 65535.
Testing Functions
The testing menu only contains one entry, the view menu. This allows you to view the status of zones and
trouble zones, control PGM's and control doors. To enter the testing menu select [MENU, 4, 8, 2] you can then
scroll the menu for the available options.
Viewing Zones
To access the zone view menu login using a valid installer code and then select [MENU, 4, 8, 2, 1, 1]. The
screen displays "Select zone to view" as shown in the following example.
Select zone to
view: CP001:01
Type the appropriate module type, module address and zone number or use the [Ð] and [Ï] keys to scroll the
available zones. When the desired zone number appears on the screen, press [ENTER] to view the selected
zone number.
When selecting a Zone the zone address is entered using the Module Type, Module Address and the number of
the zone, this is called Protege Object Notation.
Information on the Protege Object Notation and how it applies to programmable objects within the Protege
System refer to the Object Notation Section (see page 330).