Specifications
190 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Secondary Port
The Secondary port configures the reporting service with the remote port number to communicate on for the
secondary IP. By using this information in connection with the secondary IP a specific route can be set for this
connection.
SV001 Primary
port: 09647
To modify the port configuration use the keypad as explained in section Entering Decimal Numbers (see page
333) and Press [ENTER] to save the modified data.
Back Up Service
A back up service can be programmed to allow the IP reporting functions to be backed up by a telephone dialer
or similar. Using a back up service can be beneficial to allow link failures and internet access to be reported over
an alternate connection.
SV001 Back Up
None
Use the [1] and [3] keys to scroll the service selection and press [ENTER] to select the service to be used for
back up. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Back up Service Time
If both IP connections fail, the Report IP service will switch to a back up service operating over another media.
The time before this occurs can be set using the 'Backup time' setting.
SV005 Backup
time: 00030 secs
To modify the time until backup (00001 to 65535 seconds), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
Server Polling Time
The polling time is set to schedule periodic connections with the server. The polling messages sent to the
receiver will depend on the format. Some formats require that the polling time be set at both the controller and
receivers, in this case ensure that this setting matches the setting provided by the central monitoring station
company.
SV001 Polling
time: 120 secs
Edit the polling time to a value of 10 to 255 seconds, any number below 10 will disable the polling being sent to
the server. Use the keypad as explained in section Entering Decimal Numbers (see page 333) and press
[ENTER].
i
The polling time set will periodically send the polling message for the AlarmNZ IP and Patriot LS30
reporting formats a standard contact ID message with the code 602 will be sent for area 00 and point
999. In some cases these are used only to reset a polling time and not generated as alarms in the
Central Station.