Specifications
186 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Intercom Valid Data PGM
The Intercom Valid data output is activated when a packet is decoded correctly. This output will activate
regardless of the user being checked and is used to signal a "valid decode" has occurred. The PGM is not
deactivated and should have a time set in its PGM programming properties to turn off.
SV001 Valid
pgm: --000:00
To modify the Valid Data PGM, use the settings as explained in section Entering PGM and PGM Groups
(see
page 336).
Intercom Access PGM
The Intercom Access output is activated when a packet is decoded correctly and the user is found in the
system. The PGM is not deactivated and should have a time set in its PGM programming properties to turn off.
SV001 Access
pgm: --000:00
To modify the Access PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
GSM Modem Reporting Service
To program the GSM Modem service ensure that the service that has been selected is halted. Press the
[ENTER] key until the display shows the service type selection screen.
SV001 Ser Type
GSM Modem
Use the [1] and [3] keys to scroll the service types until you reach the GSM Modem selection and press
[ENTER]. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
i
The GSM Modem type that is connected must conform to the AT command set defined by the
Cellular Modem Standard. We recommend the Wavecom Fast Track modem or similar with a suitable
SEPARATE power supply and battery back-up. Do not power the modem unit from the Controller
Power Supply.
Communications Port Number
The communications interface port defines which serial port the controller will use for communication with the
GSM Modem that has been configured. Select the communication port that will be plugged in to the intercoms
communication interface or RS232 connection.
SV001 Port
Ext Port 1
Use the [1] and [3] keys to scroll the communication ports and press [ENTER] to select the port displayed. For
more information about the list control data entry refer to the section List Control Data Entry (see page 335).