Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 185
Elevator Group
The elevator group that is assigned to this service will be sent the floor group that is programmed in the user
access level settings. The elevator group settings in a user are ignored as they may have more elevators
available which are not be controlled by the intercom system.
In the case where a bank of 3 elevators are being controlled the elevator group would have the 3 elevators
selected in the elevator group. This will result in the floor assigned in the access level of the intercom user being
sent to all the elevators in the group.
SV001 Elv Group
None
Use the [1] and [3] keys to scroll the elevator group setting and press [ENTER] to select the elevator group
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Door Group
The door group that is assigned to this service will be unlocked when a valid user is found. This action is
independent of the elevator function. The user does not need to have the doors that are assigned in this door
group in the door group assigned to their access level. The door group will be unlocked independent of a user
setting.
The doors in the door group will be unlocked for the duration of the door lock time setting in each door.
This allows a user to activate the intercom have access granted from the phone system and then the access
control system grant access, allowing an event log to be generated of who let someone in to a foyer door,
additionally this information can be posted to a DVR or Text Capture software application.
SV001 Door Group
None
Use the [1] and [3] keys to scroll the door group setting and press [ENTER] to select the door group displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
Inter Byte Time
The Inter Byte time sets the idle communications time before communications is reset by the Intercom Service.
This is used when an intercom does not behave well and sends broken data that has an idle time between
bytes. This setting allows a fragmented data packet to still operate correctly. This is typical of some intercoms
that send information using proprietary modem and link devices.
SV001 Inter Byte
time: 004 secs
To modify the inter byte time (000 to 255, a setting of 000 will result in the default of 4 seconds being used), use
the keypad as explained in section Entering Decimal Numbers (see page 333) and press [ENTER].
User Offset
When the validation of the user number is set to be an offset from the code that is entered the offset quantity
needs to be entered in this screen. The offset amount is calculated as the number received from the intercom
plus this value (Intercom Packet + Offset Number = User Number).
SV001 Offset
value: 00000
To modify the offset value (00000 to 65535), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER].