Specifications
178 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Fail To Poll Time
The fail to poll time allows a timer to be triggered on each successful poll from the ModBUS Master. When this
timer expires the Fail To Poll PGM output will also be activated.
SV001 Poll fail
time: 120 secs
To modify the poll fail time (000 to 255, a setting of 000 will result in the default of 120 seconds being used), use
the keypad as explained in section Entering Decimal Numbers (see page 333) and press [ENTER].
Fail To Poll PGM Output
The fail to poll PGM output is activated when the ModBUS service poll fail timer expires and is deactivated when
the ModBUS service completes a valid communication. This PGM setting can be used to trigger an audible
alarm or other indication that ModBUS communication has failed to operate.
SV001 Poll fail
pgm: --000:00
To modify the poll fail PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
ModBUS Door Control Group
The door control group will define which doors can be controlled by the ModBUS interface if a door unlock or
lock action is requested. The default setting of None allows all doors to be controlled by the interface.
SV001 Door Grp
None
Use the [1] and [3] keys to scroll the available door groups and press [ENTER] to select the door group
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
ModBUS Area Control Group
The area control group will define which areas can be controlled by the ModBUS interface if a area disarm or
arm action is requested. The default setting of None allows all areas to be controlled by the interface.
SV001 Area Grp
None
Use the [1] and [3] keys to scroll the available area groups and press [ENTER] to select the area group
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
ModBUS Remote Reporting Service
To program the ModBUS remote reporting service ensure that the service that has been selected is halted.
Press the [ENTER] key until the display shows the service type selection screen.
SV001 Ser Type
ModBUS (Remote)
Use the [1] and [3] keys to scroll the service types until you reach the ModBUS remote reporting selection and
press [ENTER] to select the ModBUS remote reporting type displayed and proceed to the next programmable
option for the ModBUS remote reporting service. For more information about the list control data entry refer to
the section List Control Data Entry (see page 335).