Specifications
176 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Service Mode
The service mode determines how this service operates with the system controller. By default a service is set to
start with the operating system. Setting a service to "Start With The Operating System" (Start With O/S) allows
the service to operate automatically, if the system controller is reset or restarts. Manual control of the service
can be set by using the Manual option for the service mode.
SV001 Ser Mode
Start with O/S
Use the [1] and [3] keys to scroll the available operating modes and press [ENTER] to select the operating mode
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Communications Port Number
The communications interface port defines which serial port the controller will use for communication with the
ModBUS Master Controller or SCADA application. Select the communication port that will be plugged in to the
ModBUS connection.
SV001 Port
Ext Port 1
Use the [1] and [3] keys to scroll the communication ports and press [ENTER] to select the operating mode
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Communications Port Speed
The communications port speed defines the baud rate at which the ModBUS service will operate. The default
value for ModBUS is 9600 bits per second. If the speed or configuration is different adjust this setting to suit the
ModBUS master configuration.
SV001 Speed
9600
Use the [1] and [3] keys to scroll the communication port speed options and press [ENTER] to select the speed
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Communications Port Parity
The communications port parity defines the parity configuration for the communication with the ModBUS
master. This will default to Even Parity however this can be adjusted to suit the ModBUS master configuration.
SV001 Parity
Even Parity
Use the [1] and [3] keys to scroll the communication parity options and press [ENTER] to select the parity
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).