Specifications

166 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Phone Number One
The primary phone number will be dialed by the SIA service when it first is initiated to report an event. The
sequence of telephone number dialing is limited by the number of dialing attempts and the method of dialing
that is configured (alternate or sequential).
SV001 Phone 1
None
Use the [1] and [3] keys to scroll the available phone numbers and press [ENTER] to select the phone number
displayed. To program a phone number select [MENU, 4, 7, 2]. For more information about the list control
data entry refer to the section List Control Data Entry (see page 335).
Phone Number Two
The secondary phone number will be dialed by the SIA service if a connection with the central station can not be
made on the primary phone number. This may be dialled after the total number of attempts is reached on the
primary or until the total number of attempts is reached for the primary and secondary numbers. The sequence
of telephone number dialing is limited by the number of dialing attempts and the method of dialing that is
configured (alternate or sequential).
SV001 Phone 2
None
Use the [1] and [3] keys to scroll the available phone numbers and press [ENTER] to select the phone number
displayed. To program a phone number select [MENU, 4, 7, 2]. For more information about the list control
data entry refer to the section List Control Data Entry (see page 335).
Backup Phone Number
The backup phone number will be dialed by the SIA service if a connection with the central station can not be
made on either of the programmed phone numbers. This will be dialled after the total number of attempts is
reached. The backup number will be dialled for the configured number of dialing attempts programmed for the
service. For information on the dialing sequence refer to the section Sequential Dialing Attempts (see page 198)
and Alternate Dialing Attempts (see page 199).
SV001 Backup
None
Use the [1] and [3] keys to scroll the available phone numbers and press [ENTER] to select the phone number
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Dial Options
The dial options configure the service as to how it is meant to dial when a reportable event has been generated.
SV001 Dial
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 330).
Option 1 - Alternate Dialing Configuration
y Enabled the dialer will use the alternate dialing method. Refer to the Alternate Dialing (see page 199).
y Disabled the dialer will use sequential dialing method. Refer to the Sequential Dialing (see page 198).
Option 2 – Dial Number Using Pulse Dialing
y Enabled the dialer will use pulse dialing to dial out.
y Disabled the dialer will always use DTMF to dial except when Option 3 has been enabled.