Specifications

162 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Server IP Address
The Server IP Address is the IP address of the Protege System Management Suite that the Controller reports
events to when the server is not connected.
SV001 Server IP
000.000.000.000
To modify the IP address use the keypad as explained in section Entering Decimal Numbers (see page 333).
Press [ENTER] to save the Octet that is being entered and move to the next Octet or the next screen once all
four have been completed.
Server Port
The server port configures the service with the remote port number to communicate on.
SV001 Server
port: 10002
To modify the TCP/IP port (00000 to 65535), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER].
Backup IP Address
The Backup IP Address is the Backup IP address of the Protege System Management Suite that the Controller
reports events to when the server is not connected. Note that this is not a separate server, rather an alternate
path for communicating with the server.
SV001 Backup IP
000.000.000.000
To modify the IP address use the keypad as explained in section Entering Decimal Numbers (see page 333).
Press [ENTER] to save the Octet that is being entered and move to the next Octet or the next screen once all
four have been completed.
Backup Port
The backup port configures the service with the remote port number to communicate on.
SV001 Server
port: 10002
To modify the TCP/IP port (00000 to 65535), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER].
Transmit Threshold
The transmit threshold configures the service with the number of events that need to be generated before they
are transmitted to the Protege Management Suite. Leave this set to 001 to have events sent immediately.
SV001 Transmit
threshold: 001
To modify the threshold (000 to 255), use the keypad as explained in section Entering Decimal Numbers (see
page 333) and press [ENTER].