Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 151
Service Type Function
ModBUS (Remote) The ModBUS remote protocol communicates with a remote Protege System using
intelligent on-demand reporting for large scale, wide area monitoring using a standard
SCADA package while adding the ability to protect and control access to the remote
outstation.
Monitor Phone Monitors the onboard modem for incoming upload/download connections, performs
line fault monitoring and pc callback functions.
This service will share the modem with the Contact ID, SIA and ModBUS Remote and
other services that use the onboard modem if they are running.
Report IP Allows the Protege System controller to send alarm and activation information over an
IP connected network. The Report IP Service supports multiple formats and allows
the connection to third party reporting if required.
Serial Printer Prints events to a standard serial communication port. Can be programmed to only
print specific event groups or events from a specific area. Option to send
Hexadecimal Events and PC acknowledgement functions for use with Third Party
OEM event retrieval systems.
SIA Sends alarms, tests and events using the SIA Level 2 reporting format to a monitoring
station capable of receiving the SIA Level 2 format. This service shares the modem
with the Contact ID, Monitor Phone and ModBUS remote services if they are running.
Upload Direct Provides the interface between the System Controller and the Protege System
Management Suite Software. This service must always be present.
Viz IP Provides an interface for Protege System Controllers to communicate to a DVR over
IP that has the VizIP IP communication protocol. This service maps PGMs on the
System Controller to the alarm outputs from the DVR, eliminating the need to have
physical wiring connections from the DVR to the Protege System Controller.
The services require specific programming for the type that is selected, the following details the programming
information for each service type.
Contact ID Reporting Service
To program the contact ID reporting service ensure that the service you have selected it halted. Select the
service type selection screen as shown below for Contact ID.
SV001 Ser Type
Contact ID
Use the [1] and [3] keys to scroll the service types until you reach the contact ID selection and press [ENTER] to
select the contact id service type displayed and proceed to the next programmable option for the contact ID
service. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Service Mode
The service mode determines how this service operates with the system controller. By default a service is set to
start with the operating system. Setting a service to Start With The Operating System (Start With O/S) allows the
service to operate automatically, if the system controller is reset or restarts the service will automatically restart
with the operating system. To only start and stop the service manually select the manual option.
SV001 Ser Mode
Start with O/S
Use the [1] and [3] keys to scroll the available operating modes and press [ENTER] to select the operating mode
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).