Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 143
Floor Operation Schedule
The floor operation schedule can be assigned to each floor allowing the floor to unlock at the programmed times
within the schedule. A schedule is valid when the time of day falls between any start and end time provided the
day of the week is selected and holidays are not affecting the schedule. For more information on the
programming of the schedule refer to the Schedule Programming section (see page 272).
FL001 Schedule
None
Use the [1] and [3] keys to scroll the schedule selection and press [ENTER] to select the schedule displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
A schedule selection of NONE will disable the floor unlock schedule and no action will be taken on the floor.
Floor Area
The floor area defines which area is on the inside of this floor. This is used to prevent a user from gaining access
to a floor when the area is armed and they can not disarm it as well as automatically disarming the area when
the floor is accessed. Using the floor and area control integrates the two systems and is an ideal solution for
false alarm prevention.
FL001 Area
None
Use the [1] and [3] keys to scroll the floor area selection and press [ENTER] to select the floor area displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
General Options
General options configure the floor for various operational modes and functions.
EL001 General
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 – Unlock Elevator Floor Late To Open
y Enabled the floor will only be unlocked on schedule if a valid access has been made to the selected floor.
i
Unlock late to open will only operate if the elevator is configured for destination reporting and a
PRT-PX16-DRI is present.
y Disabled the floor will follow the floor schedule if programmed.
Option 2 – Validate Schedule Every Minute
y Enabled the floor state will be checked against the schedule every minute and change state accordingly.
y Disabled the floor will unlock at the start time of the schedule and lock at the end time. The floor will not be
controlled during this time by the schedule.
Option 3 – Follow Area Status
y Enabled the floor will follow the status of the area. If the area is armed the floor will lock and if the area is
disarmed the floor will unlock.
y Disabled the floor will not follow the area status.
Option 4, 5, 6, 7 and 8 - Reserved
y Reserved do not modify