Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 137
Option 4 – Deny Entry if Inside Area Armed
y Enabled the door will deny any entry if the inside area is armed.
y Disabled the inside area will not affect the access decision.
Option 5 – Deny Exit if Outside Area Armed
y Enabled the door will prevent any exit if the outside area is armed.
y Disabled the outside area will not affect the access decision.
Option 6 – Disable Door Open Alarms if unlocked on Schedule, Latch or Area Status
y Enabled the door will not generate the door left open alarm events to the reader expanders beeper and led
ports if they are programmed. This allows a door to be "propped" open during normal opening times
however a pre-alarm warning will still be generated.
This option DOES NOT prevent the door left open trouble zone from being sent to the monitoring station if
reporting on the trouble zone is programmed to be generated. To prevent the door open alarms from being
sent schedule the zone type for the door open alarm events to operate without reporting during the day.
y Disabled the door open alarm events operate normally.
Option 7 – Prompt User Access Type
y Enabled the user will be prompted on the reader expanders associated keypad to enter their reason for
access. The user must enter the reason before access will be granted.
y Disabled no prompt will be displayed.
Option 8 - Generate User Access Taken Events
y Enabled the door will generate a User Access Taken event if the door opens while the door is unlocked after
entry has been granted. If the door remains closed an Access Not Taken event will be generated.
y Disabled no event will be generated.
Access Time
Typically a door will unlock for a maximum of 5 seconds. Some users, especially the physically impaired, may
find this time too short so it is possible to extend the door access time by entering a value into the Door
Extended Access Time box. The value entered is in seconds. The door will unlock for the specified time only if
the User who accesses the door is configured as an Extended Access user (configured under the Users
options).
DR001 Extnd Axs
time: 00005 secs
To modify the Extended Access time (00001 to 65535 seconds), use the keypad as explained in section
Entering Decimal Numbers (see page 333) and press [ENTER].
Timed Anti-passback
If the Door Type assigned to the Door has anti-passback enabled then the door can have a specific
anti-passback time assigned for Entry and another time for Exit. When a user uses the door for Entry or for Exit
the time period begins and the user will not be granted repeat access to the door until the time has expired. The
time is set in minutes. This function is qualified by the global flag
Enable Timed User Anti-Passback Reset
which
is set under the Panel properties/Options settings.
DR001 PassEntry
time: 65535 mins
DR001 PassExit
time: 65535 mins
To modify the Pass Entry and Pass Exit time (00001 to 65534 minutes), use the keypad as explained in section
Entering Decimal Numbers (see page 333) and press [ENTER]. A value of 65535 will disable this function.