Specifications

134 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Forced Open PGM or PGM Group
You can assign a PGM or PGM group that will activate when the door is forced open without any access. Use
this feature to activate a local PGM at the door indicating it has been forced.
To generate an alarm on a forced door use the forced door trouble zone and assign this to an area so that a
report can be sent to a monitoring station or locally control computer.
DR001 Forced
pgm: --000:00
To modify the forced open PGM or PGM Group, use the settings as explained in section Entering PGM and
PGM Groups (see page 336).
Forced Open PGM Pulse ON Time
The forced open PGM pulse on time is used to make the PGM output pulse on and off when activated. The
value entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the
unit on for 1 second and then off for the programmed time set in the pulse off section.
DR001 Forced
time: 000 on
To modify the forced open pulse on time (000 to 255 100ms Increments), use the keypad as explained in
section Entering Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must
have a value greater than 000 for this feature to operate.
Forced Open PGM Pulse OFF Time
The forced open PGM pulse off time is used to make the PGM output pulse on and off when activated. The
value entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the
unit off for 1 second and then on for the programmed time set in the pulse on section.
DR001 Forced
time: 000 off
To modify the forced open pulse off time (000 to 255 100ms Increments), use the keypad as explained in
section Entering Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must
have a value greater than 000 for this feature to operate.
Miscellaneous Options
Miscellaneous options for the door include the control of events that are generated and the function of the door
schedule.
DR001 Misc
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Check Schedule Each Minute
y Enabled the door will revalidate the unlock schedule that it is assigned each minute. This will prevent the
door from being controlled and locked when it should be unlocked.
This option also prevents schedule and area control from operating correctly and if enabled will prevent the
follow inside and follow outside area status from operating. Setting this option will allow the prevent unlock
on arming and normal scheduling operations to occur.
y Disabled the schedule will operate normally and be checked at the start and end times.