Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 125
Use this option when multiple areas are assigned the same child area that needs to be controlled with a
specific disarming and arming order. This effectively allows an OR and AND operation to be done on the
child area.
y Disabled the child area, if option 3 is enabled, will be armed when the parent (this) area arms.
Option 5 - Disarm Child Area
y Enabled the child area will only be disarmed when the parent (this) area disarms.
y Disabled the child area will not be disarmed and option 6 performs no function.
Option 6 - Disarm Child Area Only If All Disarmed
y Enabled the child area will only be disarmed if ALL the areas that the child area are assigned are disarmed.
Use this option when multiple areas are assigned the same child area that needs to be controlled with a
specific disarming and arming order. This effectively allows an OR and AND operation to be done on the
child area.
y Disabled the child area, if option 5 is enabled, will be disarmed when the parent (this) area arms.
Option 7 - Prevent None Force Zone On Unattended Arming
y Enabled the area will be prevented from arming if a zone that is not a force enabled zone is open when the
area is armed in an unattended mode (Software Control, Reader Control or Remote Control).
y Disabled the area will arm regardless of the zone type configuration used.
Option 8 - Area Used For Loiter Control
y Enabled the area will control the users that access the area for a period of time assigned to the loiter control
time. If a user breaches the allocated time the user will be set to the area programmed in the loiter area
setting.
y Disabled the area does not operate as a loiter area.
Area Reporting Options
Reporting options for the area include the settings for the reporting events and some specific options for the
control counting options.
AR001 Report
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Report Closing (Arming) Area
y Enabled the area will generate a reportable event that can be directed to a monitoring station.
y Disabled the area will not generate an event when it is closed (armed).
Option 2 - Report Opening (Disarming) Area
y When enabled the area will generate a reportable event that can be sent to a monitoring station.
y Disabled the area will not generate an event when it is opened (disarmed).
Option 3 - Report Control of the 24HR Tamper Area
y Enabled the area will report both an opening (Disabled) or closing (Enabling) of the 24HR section of this
area.
y Disabled the 24HR Tamper Area will not report any enable or disable messages.
Option 4 - Report Bypassed Zones
y Enabled the area will report all zones that are bypassed once it completes the arming process.
y Disabled the area will not report any bypass zones.