Specifications
124 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Normal Operating Schedule
The normal operating schedule defines the times when the area should be armed and disarmed. This is used
to generate the Early/Late to Arm and Disarm Events (see Special Options (see page 127) to enable these
events).
AR001 Normal Sch
None
Period 1 of the schedule defines the time period when the area can be disarmed (Option 5 of the Special
Options must be enabled for these events to be generated).
y If the area is disarmed before the start of Period 1 an Early to Disarm event will be generated.
y If the area is still armed when Period 1 ends the System will generate a Late to Disarm event.
y No event is generated is the area is disarmed while Period 1 of the schedule is valid.
Period 2 defines the time period when the area can be armed (Option 6 of the Special Optioning must be
enabled for these events to be generated).
y If the area is armed before the start of Period 2 an Early to Arm event will be generated.
y If the area is still disarmed when Period 2 ends the System will generate a Late to Arm event.
y No event is generated is the area is armed while Period 2 of the schedule is valid.
Area Miscellaneous Options
Miscellaneous options for the area include the settings for the restore on bell, child area operations, zone forcing
and loiter mode control.
AR001 Misc
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Restore Zones After Bell Time
y Enabled the zones that are assigned to this area will restore when the bell time completes. This does not
prevent the zone from generating multiple alarms for another area this setting is specific to the area
assigned.
The zones in the area will still log an event regardless of the bell time to prevent a zone from triggering an
event remove the event log option in the zone configuration.
Setting this option will PREVENT the retrigger bell timer from operating in the zone type, do not use this
option for an area that is used for automation control or motion controlled lighting.
y Disabled the zones for the bell will restore each time the zone restores.
Option 2 - Rearm Area If Disarmed
y When enabled the area will re-arm if the area is disarmed. This feature is used for dead man timers and
areas that should not remain disarmed for a longer than a predefined time.
For this option to operate the re-arm time must be set to a value greater than 0.
y Disabled the re-arm operation will not function.
Option 3 - Arm Child Area
y Enabled the child area will be armed when the parent (this) area is armed. Please refer option 4 as this will
determine when the area is armed.
y Disabled the child area will not be armed and option 4 will perform no function.
Option 4 - Arm Child Area Only If All Armed
y Enabled the child area will only be armed if ALL the areas that the child area are assigned are armed.