Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 123
Defer PGM Pulse OFF Time
The defer PGM pulse off time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit off
for 1 second and then on for the programmed time set in the pulse on section.
AR001 Defer arm
time: 000 off
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must have a value
greater than 000 for this feature to operate.
Defer Arming Warning Time
The defer arming warning time sets the time that the area will warn the user that it is about to arm and that they
need to defer the arming (login and press the Disarm Key).
AR001 Defer warn
time: 000 off
To modify the defer warning time (000 to 255 Minutes), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
Defer Keypad Display Group
The defer keypad group is used to display that an area is about to arm on the keypads that belong to the
keypad group. The keypads will display this message provided they do not have any higher priority messages
that are being displayed. The keypad beeper is recommended to be programmed in the defer PGM output
group.
For the Defer Keypad group to generate a message the keypad must also be programmed with the Display
Defer Messages.
AR001 Defer Grp
None
Use the [1] and [3] keys to scroll the keypad group selection and press [ENTER] to select the keypad group
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Client Code
The client code for the area is the code that will be used to report alarms to the monitoring station. If the client
code is left at the default value of FFFF then the client code that will be used is the client code assigned in the
service that is being used to report the alarms.
AR001 Client
code: FFFF
To modify the client code setting (0000 to FFFF hexadecimal), use the keypad as explained in section Entering
Hexadecimal Numbers (see page 335) and press [ENTER].
Lock Door Group on Arming
When programmed this door group will be locked before the arming process starts. This helps to ensure that
any door left open zones are closed as the associated doors are locked and the area will be able to arm
successfully.
AR001 Lock Dr Gp
None