Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 117
Entry Delay PGM Pulse OFF Time
The entry delay PGM pulse off time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit off
for 1 second and then on for the programmed time set in the pulse on section.
AR001 Entry
time: 000 off
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
Both the on and off pulse settings must have a value greater than 000 for this feature to operate.
Exit Delay PGM or PGM Group
You can assign an exit delay PGM or PGM group to activate whenever the area starts an exit delay cycle. The
exit delay PGM or PGM Group will be deactivated when the area completes the arming cycle or if an alarm
occurs during the exit delay period. Disarming the area will also result in the exit delay PGM or PGM group being
deactivated.
AR001 Exit
pgm: --000:00
To modify the Exit Delay PGM or PGM Group, use the settings as explained in section Entering PGM and PGM
Groups (see page 336).
Exit Delay PGM Pulse ON Time
The exit delay PGM pulse on time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit on
for 1 second and then off for the programmed time set in the pulse off section.
AR001 Exit
time: 000 on
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must have a value
greater than 000 for this feature to operate.
Exit Delay PGM Pulse OFF Time
The exit delay PGM pulse off time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit off
for 1 second and then on for the programmed time set in the pulse on section.
AR001 Exit
time: 000 off
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must have a value
greater than 000 for this feature to operate.