Specifications
116 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Bell PGM Pulse ON Time
The bell/siren pulse on time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit on
for 1 second and then off for the programmed time set in the pulse off section.
AR001 Bell
time: 000 on
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must have a value
greater than 000 for this feature to operate.
Bell PGM Pulse OFF Time
The bell/siren pulse of time is used to make the PGM output pulse on and off when activated. The value entered
here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit off for 1
second and then on for the programmed time set in the pulse on section.
AR001 Bell
time: 000 off
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
Both the on and off pulse settings must have a value greater than 000 for this feature to operate.
Entry Delay PGM or PGM Group
You can assign a entry delay PGM or PGM group to activate whenever the area starts an entry delay cycle. The
entry delay PGM or PGM Group will be deactivated when the area is disarmed during the entry delay period or
the area activates the alarm due to the entry delay timing out.
AR001 Entry
pgm: --000:00
To modify the Entry Delay PGM or PGM Group, use the settings as explained in section Entering PGM and PGM
Groups (see page 336).
Entry Delay PGM Pulse ON Time
The entry delay PGM pulse on time is used to make the PGM output pulse on and off when activated. The value
entered here must be greater than 0 and is in increments of 100ms. For example setting 10 will pulse the unit on
for 1 second and then off for the programmed time set in the pulse off section.
AR001 Entry
time: 000 on
To modify the pulse on time (000 to 255 100ms Increments), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Both the on and off pulse settings must have a value
greater than 000 for this feature to operate.