Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 113
Re-Arm Delay
Setting the re-arm delay will result in the area automatically re-arming after the re-arm timer has elapsed. This
should be programmed for area's used to monitor and control system functions that should not be disarmed.
This is also used to control vault and automatic teller machines when using the banking area functions to
prevent an area from being disarmed for longer than a the time programmed.
AR001 Re-arm on
time: 030 mins
To enter a re-arm delay time (000 to 250 minutes), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER]. For the re-arm timer to operate the re-arm option must be
enabled.
Arming/Disarming Schedule
The arming and disarming schedule is programmed so that an area will be armed and disarmed according to a
schedule that is assigned.
The area will be disarmed at the start time and armed at the end time of the schedule.
In the case that an area only requires to be disarmed program the start time with the time that is required to
disarm and the end time of the schedule with --:--. This will mean the area will automatically disarm at the start
time for the programmed days in the period.
Do the same if the area requires to be armed only on schedule by programming the end period with the required
time to arm and set the start time to --:--.
AR001 Schedule
None
Use the [1] and [3] keys to scroll the schedule selection and press [ENTER] to select the schedule displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
Recent Close Time
The recent closing time defines how long the system considers an armed area recently closed. If, after arming
the area, an alarm is generated within the programmed period, the Protege System Controller transmits a recent
closed message. For this feature to operate correctly the zone must have its report options enabled in the
assigned zone type.
AR001 Recent cls
time: 000 secs
To enter a recent closing delay time (000 to 250 minutes), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER]. Setting a value of 000 will result in no recent closing
reports being sent for the area.
Disarm Delay Time
The disarm delay time is used in conjunction with the Automatic Teller Machine control and banking control
functions. Setting a disarm delay time will cause the area to delay by the programmed delay time any access to
the area.
AR001 Disarm dly
time: 000 mins
To enter a disarm delay time (000 to 250 minutes), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].