Specifications
112 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Area Entry Delay Time
Setting an entry delay time for the area allows users that have entered a secured point to have time to disarm
the area before the area generates an alarm. Only zones that have a zone type assigned with an entry delay
option set will start the entry delay timer for the area.
AR001 Entry
time: 060 secs
To enter a entry delay time (000 to 250), use the keypad as explained in section Entering Decimal Numbers (see
page 333) and press [ENTER].
Area Exit Delay Time
Setting an exit delay time for the area allows users to exit the area once the arming of the area has begun
without triggering an alarm. Zones that are part of the exit route should be programmed with the exit option in
the assigned zone type.
AR001 Exit
time: 030 secs
To enter a exit delay time (000 to 250), use the keypad as explained in section Entering Decimal Numbers (see
page 333) and press [ENTER]. An exit delay time of 000 seconds will result in the area arming instantly.
Area Siren Bell Time
The bell time determines how long the bell/siren output for the area will remain activated before timing out. If the
option to retrigger the bell time is set in the zone type assigned to a zone that is triggered in the area the siren
bell time is reloaded on each subsequent alarm activation.
Use the siren bell time and the retrigger bell option from the zone type for smart automation of lighting and
building control.
AR001 Bell
time: 004 mins
To enter a bell siren time (000 to 250 minutes), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER]. A bell siren time of 000 will result in no siren or bell activation.
Intelligent False Alarm Prevention Time
Setting an intelligent false alarm prevention time allows the area to process alarms using smart alarm verification.
For an alarm to occur in the area it will require that the same zone generate more than one alarm in a time
programmed or that any other zone that is not assigned the intelligent false alarm prevention time generates an
alarm.
AR001 Intel zone
time: 000 secs
To enter an intelligent false alarm prevention time (000 to 250 seconds), use the keypad as explained in section
Entering Decimal Numbers (see page 333) and press [ENTER]. Setting the intelligent false alarm prevention time
to a value of 000 will result in any intelligent false alarm prevention zone from activating normally.