Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 109
Activation Schedule
The activation schedule is programmed to activate the PGM at a certain time of the day or to activate the PGM
between certain hours. The schedule will be checked at the start and end times and if the start is valid the PGM
will be activated, if the end time of the schedule is valid the PGM will be deactivated.
If a PGM is controlled by an operator, user or other function during this activation time and is deactivated it will
remain in the deactivated state. Setting the recheck schedule option for the PGM will force the PGM to have the
schedule verified every 60 second period. This will prevent the PGM from being controlled manually as the
schedule will override the manual operation.
CP001:01 Sched
None
Use the [1] and [3] keys to scroll the schedule selection and press [ENTER] to select the schedule displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
PGM Activation Time
Setting an activation time for a PGM will mean that any device controlling the PGM will only activate the PGM for
the programmed time.
CP001:01 Pgm
time: 00000 secs
To enter a activation time (00000 to 65535), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER].
PGM Miscellaneous Options
Miscellaneous options for the PGM include the configuration of event logging, schedule and power up
configurations for the PGM.
CP001:01 Misc
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Log PGM Event
y Enabled the PGM will generate an event whenever it is activate or deactivated.
The PGM will still perform all functions that are programmed if this is not enabled. When using PGM's as
automation control outputs it is recommended to disable the event logging option to reduce the impact on
the event log buffer.
y Disabled the PGM will not log an event.
Option 2 - Verify Schedule State
y When enabled the PGM will re verify the schedule that is programmed every 60 seconds. If the PGM is
meant to be activated but is in a deactivated state the system will activate the PGM.
y Disabled the PGM will only activate at the start time and the end time of the programmed schedule.
Option 3 - Change PGM State at Panel Reset
y Enabled the PGM will be set to the state that is selected by option four when the panel is reset or powers
up for the first time. By default this option is enabled and all PGM's will be set to the deactivated state.
y Disabled the PGM state will not be changed from when the panel was reset or powered down.
Option 4 - PGM State Setting
y Enabled the PGM will be activated if option three is enabled.
y Disabled the PGM will be deactivated if option three is enabled.