Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 103
Zone Type Miscellaneous Options
Miscellaneous options for the zone type configure options for various functions.
ZT001 Misc
[1-3-----]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Generate Siren Bell Output
y Enabled the zone type will activate the siren bell output programmed for the area.
y Disabled the zone type will not generate a bell output.
Option 2 - Restart Siren Bell Timer
y Enabled the zone type will restart the bell timer on each subsequent alarm.
y Disabled the zone type will not alter the bell timer if it is already active.
Option 3 - Save Alarm to Memory
y Enabled the zone type will save an alarm message to the area's alarm memory storage area.
y Disabled the zone type does not save an alarm message.
Option 4 - Disarm Control Area on Restore
y Enabled the zone type will disarm the control area when a zone assigned the zone type restores from an
alarm condition.
Use this feature and the arming control area feature as a on and off key switch arming input.
y Disabled the zone type takes no action on the control area.
Option 5 - Arm Control Area on Alarm
y Enabled the zone type will start arming the control area when a zone assigned the zone type generates an
alarm condition.
y Disabled the zone type takes no action on the control area.
Option 6 - Toggle Control Area State On Alarm
y Enabled the zone type will toggle the state of the control area when the zone that is assigned this zone type
generates an alarm.
y Disabled the zone type operates normally.
Option 7 - Force Arm Tamper
y Enabled the zone type will allow the zone to be force armed if the zone assigned the zone type is tampered.
y Disabled the zone type operates normally.
Option 8 - Activate Entry PGM For Bell Siren Time Duration
y Enabled the zone type will activate the entry PGM programmed for the area for the duration of the bell siren
time.
Use this feature for a zone that you want to only generate a beeper alarm and assign the entry PGM a
keypad beeper pgm. This option will not function if the bell option is enabled.
y Disabled the zone type operates normally.