Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 101
Zone Type Alarm Options
Alarm options for the zone type configure the operation of the zone type when an alarm, restore and tamper are
generated.
ZT001 Alarm
[12345---]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Process Alarms
y Enabled the zone type will process alarms from the zone that it is assigned.
y Disabled the zone type will perform no function on an alarm being generated.
Option 2 - Process Tamper 24HR Alarm
y Enabled the zone type will process tamper alarms from the zone that it is assigned.
y Disabled the zone type will perform no tamper processing.
Option 3 - Entry Delay
y Enabled the zone type will start an entry delay timer for the assigned area when the zone generates an
alarm.
y Disabled the zone type will not perform any entry delay actions.
Option 4 - Entry Delay Follow
y Enabled the zone type will allow this zone to generate alarms during the entry delay however it will generate
an alarm if the alarm condition occurs outside the entry delay period.
y Disabled the zone type operates normally.
Option 5 - Exit Delay Follow
y Enabled the zone type will allow this zone to generate alarms during the exit delay however it will generate
an alarm if the alarm condition occurs outside the exit delay period.
Use this feature to prevent 'Sitters' from re-entering a building that is assumed to be secure during a long
arming process.
y Disabled the zone type operates normally.
Option 6 - Shorten Exit Delay Timer On Restore
y Enabled the zone type will shorten the exit delay timer on an area to five seconds when the zone restores.
Use this feature to reduce the arming time of an area.
y Disabled the zone type operates normally.
Option 7 - 24HR Alarm
y Enabled the zone type will generate a 24HR alarm if the zone generates an alarm. The area state will not
affect the generation of this alarm.
y Disabled the zone type operates normally.
Option 8 - Fire Alarm
y Enabled the zone type will generate a fire alarm when it is activated. This zone type will also operate similar
to the 24HR Alarm option.
Most smoke detectors use a normally open contact so any zone that is assigned this option must have the
inverted state option selected and the EOL resistors option enabled.
y Disabled the zone type operates normally.