Specifications
100 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Secondary Zone Type
A secondary zone type can be selected that will be used when the schedule of the zone type that is
programmed is not valid. The schedule of the secondary zone type must be valid or set to none.
ZT001 Secondary
None
Use the [1] and [3] keys to scroll the secondary zone type selection and press [ENTER] to select the zone type
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335). Programming a secondary zone type with the current zone type being edited will perform no
function.
Zone Type Keypad Group
A zone type keypad determines which keypads will be presented with alarm information when the zone that the
zone type is assigned generates an alarm.
ZT001 Key Grp
None
Use the [1] and [3] keys to scroll the available keypad groups and press [ENTER] to select the keypad group
displayed. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
Control Area
A zone type can be programmed to control the arming and disarming state of an area from a zone input (key
switch control). The area to be controlled by the zone type must be programmed with the force arming option.
Arming using a zone type is deemed to be a unattended arming condition and therefore the system will attempt
to arm the area in the force mode.
ZT001 Ctrl Area
None
Use the [1] and [3] keys to scroll the available area's and press [ENTER] to select the area displayed. For more
information about the list control data entry refer to the section List Control Data Entry (see page 335).
Automation Control Point
An automation control point allows this zone type to control an automation point in response to a zone opening
or closing. An automation point can be assigned to many different functions such as gardening irrigation, lighting
circuits, CBus Circuits and any PGM Output. You must configure the appropriate options to trigger the
Automation point.
ZT001 Automate
None
Use the [1] and [3] keys to scroll the available automation points and press [ENTER] to select the automation
point displayed. For more information about the list control data entry refer to the section List Control Data Entry
(see page 335).