4.4 Fire Zone Input Wiring
When wiring a zone to be a Fire Zone input the current programmed Zone Opons will determine
what resistors and conguraon is required. RefertotheGeneralOponssecononpage23and
theZoneInputWiringsecononpage7.
?
When a Fire Zone is connected to a zone input that is used in the Duplex Zone
conguraon a Fire Zone fault will not be shown when the Fire Zone has a shorted
condion as this is shown as all zones closed. A Fire Loop Trouble will be shown
when the zone is tampered.
!
Fire Zones that are installed in Duplex mode operaon are not recommended.
Fire Zones should always be connected using the EOL resistor method (1k and 1k)
as this provides both open and short circuit monitoring.
?
The Protégé® EliteSuite® Eclipse LED Keypad is designed to be used with
non-latching smoke detectors. If latching smoke detectors are used then the
keypad cannot reset them automacally and a power cycle will be required.
Fire/Smoke Detec�on Unit
Fire Detec�on
Device Power
N.O. Fire Zone
Contact
NEG-
POS+
Figure 10 - Fire/Smoke Detecon Input
9