Installation manual
4.4 Fire Zone Input Wiring
When wiring a zone to be a Fire Zone input the current programmed Zone Opons will determine
what resistors and conguraon is required. RefertotheGeneralOponssecononpage23and
theZoneInputWiringsecononpage7.
?
When a Fire Zone is connected to a zone input that is used in the Duplex Zone
conguraon a Fire Zone fault will not be shown when the Fire Zone has a shorted
condion as this is shown as all zones closed. A Fire Loop Trouble will be shown
when the zone is tampered.
!
Fire Zones that are installed in Duplex mode operaon are not recommended.
Fire Zones should always be connected using the EOL resistor method (1k and 1k)
as this provides both open and short circuit monitoring.
?
The Protégé® EliteSuite® Eclipse LED Keypad is designed to be used with
non-latching smoke detectors. If latching smoke detectors are used then the
keypad cannot reset them automacally and a power cycle will be required.
Fire/Smoke Detec�on Unit
Fire Detec�on
Device Power
N.O. Fire Zone
Contact
NEG-
POS+
Figure 10 - Fire/Smoke Detecon Input
9