Instruction Manual

2
PROTECH SORADIO
1 WIRING
Note: All common inputs are connected together.
Example of input wiring:
The inputs are seen out of alarm when they are closed. They are seen in alarm when they are open
(Positive security).
* LEDs status L1, L2 et L3:
L1: green
Operating mode
OFF: Radio Mode
ON: RS485 Mode (unused in SORADIO)
LEDs active only if BLE
is activated after a short
press on the tamper
L2: orange
Radio configuration
status
Blinking: Radio mode not configured
ON: Radio mode configured
L3: red
BLE status
OFF: BLE deactivated
Blinking: BLE active waiting for connection
ON: BLE active connected to the application
Maximum length of 12V DC power supply cables:
(cable type SYT1 shielded)
Wire
Wire section
0.6 mm
0.02 in
0.3 mm²
23 AWG
500 m
0.31 mi
0.9 mm
0.04 in
0.6 mm²
20 AWG
1124 m
0.7 mi
1.4 mm
0.06 in
1.5 mm²
16 AWG
2506 m
1.56 mi
Note: When using the same cable to supply power to several components, the indicated distances should be divided
by the number of connected components. When using several wires with the same section in parallel by
polarity, the indicated distances should be multiplied by the number of connected wires.
N° Terminals
Description
1
Input 1
2
Common
3
Input 2
4
Common
5
Input 3
6
Common
7
Input 4
8
Common
9
Input 5
10
Common
11
Input 6
12
Common
13
Input 7
14
Common
15
Input 8
16
Common
17
X
18
X
19
X
20
X
21
0V Power supply
22
+12V DC Power supply
E1
C
*
L1
L2
L3