Technical data
48
Flexible Tracer Heaters
Heating Tapes
Type HKSI 70 Ni
HighTechIntegral; HTI heating tape with the
heating conductor as a sensor
On the HTI parallel heating tape, the complete length of the heating
tape is used for temperature measurement and control (integral),
with which we achieve uniform temperature measurements over
the complete area.
Additional advantage: The parallel heating tape can be cut to size in
situ and during fi tment can be especially adapted to the installation
that is to be heated.
Operating temperature:
180°C (integrally controlled)
Rated voltage:
max. 230 V AC/DC
Rated power:
70 W/m at 20°C
Surface temperature:
max. 200°C
Length of heating circuit:
max. 60 m
Contact clearance:
2 m
Min. bending radius:
50 mm
Outer dimensions:
app. 8 x 11 mm (oval)
Outer jacket:
FEP
Protection grade:
IP 65 (EN 60529)
Safety conductor braiding:
yes
Protection class:
I
Making up sets page 46
Temperature control using our integral thermostat HTI, as listed in
chapter 6 Temperature Controllers.
180 °C
FEP-Outer jacket
Saftey conductor braiding
Silicon-Insulation
Outer conductor
(Cu-Lace 2 mm
2
)
Heating coil
Silicon-Insulation
Contact clearance
Contact clearance