RLX-IH And RLX-PC-IB/EB Setup Guide 1
Table of Contents Table of Contents Table of Contents......................................................................................................................... 2 Application Objective .................................................................................... 3 Instructions ................................................................................................................ 3 1. RLX-IH Setup.................................................................................
Application Objective The purpose of this document is to aid in the setup of the RLX-IH when used in conjunction with an RLX-PC-IB/EB card. This document assumes the following: 1. The user has a general understanding of the Windows Networking Environment. 2. The user has read and understands the hardware and voltage requirements of the RLXIH. 3. The user is configuring the RLX-IH with a laptop that has an installed LAN based Ethernet adapter. If using a PC, the steps for the RLX-IH setup are similar. 4.
15. 16. 17. 18. Click on Apply Changes. Click the Close button to close the current webpage, and choose Yes to confirm. Open the RadioLinx Industrial Hotspot Browser. If you manually assigned an IP address to the RLX-IH, you should see that IP address in the RadioLinx Industrial Hotspot Browser. 19. If you specified that the RLX-IH should obtain an IP address automatically, then connect the RLX-IH to your network at this time.
6. Click on the Configuration tab. 7. For Network Name, enter the exact SSID that you entered during the RLX-IH webpage setup (step 12 in the RLX-IH Setup section). 8. Ensure Network Type is set to Access Point, Power Save Mode is off, and Transmit Rate is set to Fully Automatic. 9. Click on the Encryption tab.
10. Select either 64, or 128 bit encryption. Ensure this matches what you selected during the RLX-IH Setup, step 13. 11. Select Alphanumeric: *This will say “5 characters” for 64 bit, and “13 characters” for 128 bit*. Make the appropriate selection. 12. In Key 1, type the text key you used during the RLX-IH Setup, step 13, and ensure Use WEP Key is set to 1. 13. Click OK icon.