Register Range Parameter
5013 5 to 8 Port 1 Data Bits
5014 1, 2 Port 1 Stop Bits
5015 0 to 65535 Port 1 RTS On (mSec)
5016 0 to 65535 Port 1 RTS Off (mSec)
5017 0 to 65535 Port 1 Minimum Response Delay (mSec)
5018 0, 1 Port 1 Use CTS (Y, N)
5019 0 to 255 Port 1 Slave ID
5030 0, 1 Port 2 Enable
5031 Port 2 Baud Rate
5032 0 to 4 Port 2 Parity
5033 5 to 8 Port 2 Data Bits
5034 1, 2 Port 2 Stop Bits
5035 0 to 65535 Port 2 RTS On (mSec)
5036 0 to 65535 Port 2 RTS Off (mSec)
5037 0 to 65535 Port 2 Minimum Response Delay (mSec)
5038 0, 1 Port 2 Use CTS (Y, N)
5039 0 to 255 Port 2 Slave ID
8.4 PTQ-LNG Status Data Definition
This section contains a listing of the data contained in the PTQ-LNG status data
object.
Register Content Description
6000 Program cycle counter
This value is incremented each time a complete
program cycle occurs in the module.
6001 to 6002
Product name as ASCII
string
This register contains the product code of "LNG"
6003 to 6004
Revision level as ASCII
string
This register contains the product version for the
current software.
6005 to 6006
Operating system level as
ASCII string
This register contains the month and year values for
the program operating system.
6007 to 6008 Run number as ASCII string
This register contains the run number value for the
current software.
6009 Number of requests - Port 1
Contains the number of messages received on the
port.
6010
Number of responses - Port
1
Contains the total number of messages sent out of
the port.
6011
Number of errors sent - Port
1
Contains the total number of message errors sent out
of the port.
6012
Number of errors received -
Port 1
Contains the total number of message errors received
on the port.
6013 Number of requests - Port 2
Contains the number of messages received on the
port.