PTQ-LNG Quantum / Unity Platform Reference
Landis & Gyr Telegyr Interface Module
Page 86 of 103 ProSoft Technology, Inc.
May 29, 2007
Start Address End Address Data Quantum Address
2035 Chassis Number 2 Internal Only
2036 2051 Card Code Internal Only
2052 Chassis Number 3 Internal Only
2053 2068 Card Code Internal Only
2069 Chassis Number 4 Internal Only
2070 2085 Card Code Internal Only
2086 Chassis Number 5 Internal Only
2087 2102 Card Code Internal Only
2103 Chassis Number 6 Internal Only
2104 2119 Card Code Internal Only
5000 Configuration Internal Only
5010 5021 Port 1 Configuration Internal Only
5030 5041 Port 2 Configuration Internal Only
6000 6021 Error / Status Table Internal Only
Note: According to the protocol specification, the accumulators may assume
values of up to 65535. Because the PTQ-LNG module displays the database
values as a signed integer (-32767 to 32767), the accumulator values might
not be displayed as expected by the user. The user should display the
accumulator values in the database in hex format.
8.2.2 Module Control Blocks
As discussed in the previous section, range 4000 to 4999 in the internal
database controls the module in order to perform specific tasks. These tasks are
described in the following topics. Word 4000 contains the block ID that identifies
the block to the PTQ-LNG module. The block structure is different for each block.
8.3 Configuration Data Definition
This section contains a listing of the parameters and addresses that are available
in the PTQ-LNG database.
Register Range Parameter
5000 0 to 300 Number of Analog Inputs
5001 0 to 50 Number of Digital Input Words (16 points per word)
5002 0 to 50 Number of Accumulators
5003 0 to 50 Number if Indication Point Words
5004 0 to 65535 Backplane Fail Counter
5005 0 to 3 SBO Timer Base
5006 0 to 32767 SBO Select Time
5010 0, 1 Port 1 Enable
5011 Port 1 Baud Rate
5012 0 to 2 Port 1 Parity