Configuring the Module PTQ-LNG Quantum / Unity Platform
Landis & Gyr Telegyr Interface Module
ProSoft Technology, Inc. Page 57 of 103
May 29, 2007
Word Offset in
Block
Example
Address
Data Description
8 300108
Pulse Lower
100ms Control
Control point Lower at 100ms
9 300109
Pulse Lower
100ms
Pulse Lower at 100ms
10 300110
Pulse Raise 1s
Control
Control point Raise at 1s
11 300111 Pulse Raise 1s Pulse Raise at 1s
12 300112
Pulse Lower 1s
Control
Control point Lower at 1s
13 300113 Pulse Lower 1s Pulse Lower at 1s
14 300114
Pulse Raise 10s
Control
Control point Raise at 10s
15 300115 Pulse Raise 10s Pulse Raise at 10s
16 300116
Pulse Lower 10s
Control
Control point Lower at 10s
17 300117 Pulse Lower 10s Pulse Lower at 10s
18 300118 Pulse Point This field contain number of point selected.
In your table, word zero will contain a value of zero, word one will contain the
BLOCK ID code, and word two and so on will contain the data.
Block 9994 – Pulse Train Output
If the module retrieves a BLOCK ID of 9994 from the PLC after it is issued the
Command Function 26 by a master, it will place the pulse train output data
contained within the block into the event buffer and alter the data values for the
points in the database. Using the example data buffer of 300100 to 300199
described above the contents of the block would look as follows:
Word Offset in
Block
Example
Address
Data Description
0 300100 0
If it completed successfully. A counter will
increment.
1 300101 Block ID 9994
2 300102
Pulse Train
Operate
This field indicated that the point number
shown was in operation.
3 300103 Pulse Train Point
This field contains the value of point
controlled.
4 300104
Pulse Train
Command
This field indicated either the bit is trip or
close.
5 300105
Pulse Train On
Duration
Number of on duration in ms.
6 300106
Pulse Train Off
Duration
Number of off duration in ms
In your table, word zero will contain a value of zero, word one will contain the
BLOCK ID code, and word two and so on will contain the data.