User manual
Table Of Contents
- Start Here
- Configuring the Processor with Concept
- Configuring the Processor with ProWORX
- Configuring the Processor with UnityPro XL
- To build (compile) the project:
- To verify address and driver settings in UnityPro XL:
- Setting Up the ProTalk Module
- Configuring the Module
- Diagnostics and Troubleshooting
- Reading Status Data From the Module
- The Configuration/Debug Menu
- Required Hardware
- Required Software
- Using the Configuration/Debug Port
- Main Menu
- Opening the Data Analyzer Menu
- Viewing Block Transfer Statistics
- Viewing Module Configuration
- Opening the Database Menu
- Opening the Backplane Menu
- Transferring the Configuration File from PC to PTQ module
- Transferring the Configuration File from PTQ module to PC
- Viewing Version Information
- Warm Booting the Module
- Viewing Port Communication Status
- Viewing Port Configuration
- Exiting the Program
- Database View Menu
- Viewing Register Pages
- Displaying the Current Page of Registers Again
- Moving Back Through 5 Pages of Registers
- Viewing the Previous 100 Registers of Data
- Skipping 500 Registers of Data
- Viewing the Next 100 Registers of Data
- Viewing Data in Decimal Format
- Viewing Data in Hexadecimal Format
- Viewing Data in Floating Point Format
- Viewing Data in ASCII (Text) Format
- Returning to the Main Menu
- Backplane Menu
- Data Analyzer
- Data Analyzer Tips
- LED Status Indicators
- Reading Status Data From the Module
- Reference
- Index

Configuring the Module PTQ-LNG ♦ Quantum / Unity Platform
Landis & Gyr Telegyr Interface Module
ProSoft Technology, Inc. Page 51 of 103
May 29, 2007
Write Register Start
Write Register Start : 0 #Database start register where data placed from
#processor
The Write Register Start parameter assigns the starting address for data to
retrieve from the processor.
Write Register Count
Write Register Count : 600 #Number of registers to read from processor
This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999
3x Register Start
1 to n
This parameter sets the first register in the processor where the data transferred
from the module to the processor will be placed.
4x Register Start
1 to n
This parameter sets the first register in the processor where the data transferred
from the processor to the module is present.
Initialize Output Data
Yes or No
This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to 0, the output data will be
initialized to 0. If the value is set to 1, the data will be initialized with data from the
processor. Use of this option requires associated ladder logic to pass the data
from the processor to the module.
Failure Flag Count
Failure Flag Count : 0 #Determines module operation if BP fails
#0=continue,>0=number of retries before comm
#shutdown
This parameter specifies the number of successive transfer errors that must
occur before the communication ports are shut down. If the parameter is set to 0,
the communication ports will continue to operate under all conditions. If the value
is set larger than 0, communications will cease if the specified number of failures
occur. Valid values are 0 to 65535.
Error/Status Block Pointer
Error/Status Block Pointer : 3500 # Number of register to
# store error and status