PTQ-104S Rev2 Quantum Platform Module Configuration
IEC 60870-5-104 Server for Quantum User Manual
ProSoft Technology, Inc. Page 93 of 195
February 22, 2013
Group Code
Description
0x00010000
Interrogated by group 16 interrogation
0x00020000
Interrogated by general counter request
0x00040000
Interrogated by group 1 counter request
0x00080000
Interrogated by group 2 counter request
0x00100000
Interrogated by group 3 counter request
0x00200000
Interrogated by group 4 counter request
0x40000000
Disable event scanning of this point
0x80000000
Periodic/cyclic data returned from unit
Note 1: Group 3 interrogation also returns the parameter data (ASDU 110 threshold, low limit
and high limit) for all monitored measured points.
If the highest bit (bit 31) is set, data will be produced by the driver for the
specified point at the rate set for periodic data generation. Bit 30 (0x40000000)
enables scanning of this point for event generation. If the bit is clear and the data
type is set for scanning, events will be generated for the point. If the bit is set,
events will not be generated for the point. This feature can be used to select
which points will generate events for the controlling station and can get rid of
event data that is not important to the application.
5.25 To Create Optional Comment Entries
1 Click the plus sign to the left of the icon to expand the module
Comments.
2 Double-click the icon. The Edit - Module Comment dialog
appears.
3 Enter your comment and click OK to save your changes.