User manual
Module Configuration PTQ-104S Rev2 ♦ Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 90 of 195 ProSoft Technology, Inc.
February 22, 2013
5.18 [I104S] > [C_DC_NA_1 104]
This section defines the double point command database. This information is
sourced from the remote Client and is transferred to the database. You can
associate a command with a monitored double point database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Address values in the table. If the Require Select
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
Point #
DB Address
Monitor Point #
Monitor DB Address
Require Select
Each point is two bits and the DB Address value corresponds to the bit offset in
the module memory database. For additional information on how to set these
parameters, see the Reference chapter of this manual.
5.19 [I104S] > [C_RC_NA_1 104]
This section defines the step command database. This information is sourced
from the remote Client and is transferred to the database. The control value can
be associated with a monitored point as described in the previous example.
This section takes the following parameters:
Point #
DB Address
Monitor Point #
Monitor DB Address
Each point is one 8-bit byte and the DB Address value corresponds to the byte
offset in the module memory database. For additional information on how to set
these parameters, see the Reference chapter of this manual.
5.20 [I104S] > [C_BO_NA_1 104]
This section defines the 32-bit Bitstring command database for the server
emulated. This information is sourced from the remote Master and is transferred
to the database.
You can associate a command with a monitored double point database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Addr values in the table. If the Require Select parameter
is not set to zero, a select command must be received before an execute
command will be processed.
This section takes the following parameters:
Point #