User manual

Module Configuration PTQ-104S Rev2 Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 84 of 195 ProSoft Technology, Inc.
February 22, 2013
These parameters specify the number of point values that can be assigned for
each database.
Type ID
Point Database Description
Range
M_SP_NA
Monitored Single-Point
0 to 1000
M_DP_NA
Monitored Double-Point
0 to 1000
M_ST_NA
Monitored Step Position Point
0 to 1000
M_BO_NA
Monitored 32-bit Bitstring Data Point
0 to 1000
M_ME_NA
Monitored Normalized Measured Point
0 to 1000
M_ME_NB
Monitored Scaled Measured Point
0 to 1000
M_ME_NC
Monitored Short Floating-Point Measured Point
0 to 50
M_IT_NA
Monitored Integrated Total
0 to 99
C_SC_NA
Command Single-Point
0 to 1000
C_DC_NA
Command Double-Point
0 to 1000
C_RC_NA
Command Step Point
0 to 1000
C_BO_NA
Command 32-bit Bitstring Point
0 to 1000
C_SE_NA
Command Normalized Set Point
0 to 1000
C_SE_NB
Command Scaled Set Point
0 to 1000
C_SE_NC
Command Short Floating-Point Set Point
0 to 50
5.7.6 Sequence Flag
YES or NO
In order to save bandwidth, you can configure the module to use the Sequence
Flag feature using the following parameters:
If this parameter is set to NO, this feature is not selected, the module will send
the object address and value for every monitored point sent to the Client, and the
Sequence Flag (SQ) will be set to zero (0).