Module Configuration PTQ-104S Rev2 ♦ Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 82 of 195 ProSoft Technology, Inc.
February 22, 2013
5.7 [I104S] > [IEC-870-5-104 Database]
This section describes parameters in the [I104S]>IEC-870-5-104 Database
section.
5.7.1 Short Pulse Time
0 to 2,147,483,647 (2 raised to the power of 31) milliseconds
This parameter defines the number of milliseconds to keep an IEC Command
Point set ON, HIGH, equal to one (1), before returning the point to OFF, LOW,
equal to zero (0), whenever a pulse point command is sent by the Client and the
default value of the Default Command Qualifier parameter is set to SHORT.
5.7.2 Long Pulse Time
0 to 2,147,483,647 (2 raised to the power of 31) milliseconds
This parameter defines the number of milliseconds to keep an IEC Command
Point set ON, HIGH, equal to one (1), before returning the point to OFF, LOW,
equal to zero (0), whenever a pulse point command is sent by the Client and the
default value of the Default Command Qualifier parameter is set to LONG.