5.6.27 Time Type
0 = NONE, 1 = CP24, or 2 = CP56
Separate parameters exist for multiple point types. This parameter defines the
time format used with data events.
5.6.28 Use Recent
0 = REPORT MULTIPLE, 1 = REPORT SINGLE
This parameter determines how the events will be stored at the event queue and
reported to the remote Client. The 104S protocol supports event queues for each
data type that can store multiple, time-stamped events as they happen and report
those events to a remote Client. Some applications may require all events that
transpire be added to the queue and be reported. Other applications may require
only the most recent event of each IEC database point to be reported.