User manual

PTQ-104S Rev2 Quantum Platform Module Configuration
IEC 60870-5-104 Server for Quantum User Manual
ProSoft Technology, Inc. Page 75 of 195
February 22, 2013
5.6.12 Command Delay Timer
1000 to 60000 milliseconds
This value is used for time-tag validity verification for the ASDUs listed
below. The received commands will only be accepted if [timestamp + Command
Delay Timer] is greater than the module's own time.
58: Single command with time tag CP56Time 2a
59: Double command with time tag CP56Time 2a
60: Regulating step command with time tag CP56Time 2a
61: SetPoint command, normalized value with time tag CP56Time 2a
62: SetPoint command, scaled value with time tag CP56Time 2a
63: SetPoint command, short floating point with time tag CP56Time 2a
107: Test command with time tag CP56Time2a
If the value is less than 1000 milliseconds, the module will default to 5000
milliseconds
5.6.13 Freeze Start Type
D = DAY, H = HOUR, M = MINUTE, N = NOT USED
The Freeze Start Type parameter defines when the module starts sending the
M_IT messages.
5.6.14 Interval for Freeze
0 to 65535 seconds
Freeze Start Type and Interval for Freeze are used if Mode A operation is to be
used for the counter freeze operation. If they are not used, the module will
operate in Mode D.
5.6.15 Common Address of ASDU
0 to 65535
This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.
5.6.16 Cyclic Data Transmission
0 to 4,294,967,296 (2 raised to the power of 32)
This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permits update times of 1 millisecond to 5
minutes. If the parameter is set to 0, cyclic data reporting will be disabled.
5.6.17 Select/Operate Timeout
0 to 4,294,967,296 (2 raised to the power of 32) milliseconds