User manual

PTQ-104S Rev2 Quantum Platform Module Configuration
IEC 60870-5-104 Server for Quantum User Manual
ProSoft Technology, Inc. Page 71 of 195
February 22, 2013
5.4.3 Use Daylight Savings Time
Yes or No
This parameter specifies if daylight savings time will be used in the time
computation.
5.4.4 Database Register
-1 or 0 to 3992 as an even value
This parameter specifies if the NTP time computed by the driver is to be placed
into the module’s database. If a value of -1 is specified, the time will not be
placed into the database. If the value is between 0 and 3992, the time will be
placed in the database. The first 4 bytes will represent the seconds since
1/1/1970, and the second 4 bytes will represent the number of microseconds. An
even value should be used for the register value in order for the data to be stored
correctly.
5.5 [I104S] Section
The I104S section allows the user to setup the following features:
General Server parameters
General Database parameters
IP Access List addresses
IEC Database points for each data type