User manual

PTQ-104S Rev2 Quantum Platform Module Configuration
IEC 60870-5-104 Server for Quantum User Manual
ProSoft Technology, Inc. Page 67 of 195
February 22, 2013
Block Format for Read
Word Offset in Block
Data Field(s)
Description
1
Block ID
This word will contain the value of 9958
5.3.4 Read Module's Time to Processor (9970)
If a value of 9970 is placed in the control register, the processor will read the
module's current time.
Block Format for Write
The following table shows the block format for write:
Word Offset in Block
Data Field(s)
Description
1
Block ID
This field contains the value of 9970 identifying the
block type to the module.
Block Format for Read
The module responds to a valid 9970 request with a block containing the
requested date and time. The block format is shown in the following table.
Word Offset in Block
Data Field(s)
Description
1
Block ID
This word will contain the value of 9970.
2
Year
This field contains the four-digit year for the new time
value.
3
Month
This field contains the month value for the new time.
Valid Values: 1 to 12.
4
Day
This field contains the day value for the new time.
Valid Values: 1 to 31.
5
Hour
This field contains the hour value for the new time.
Valid Values: 0 to 23
6
Minute
This field contains the minute value for the new time.
Valid Values: 0 to 59.
7
Seconds
This field contains the second value for the new time.
Valid Values: 0 to 59.
8
Milliseconds
This field contains the millisecond value for the new
time. Valid Values: 0 to 999.