User manual

Reference PTQ-104S Rev2 Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 178 of 195 ProSoft Technology, Inc.
February 22, 2013
Type ID
Description
Type
<62>
Set point command, scaled value with
time tag CP56Time2a
C_SE_TB_1
<63>
Set point command, short float value
with time tag CP56Time2a
C_SE_TC_1
<64>
Bitstring of 32 bit with time tag
CP56Time2a
C_BO_TA_1
Either the ASDUs of the set <45>-<51> or of the set <58>-<64> are used.
System information in monitor direction
(Station-specific parameter, mark "X" if used)
Type ID
Description
Type
<70>
End of initialization
M_EI_NA_1
System information in control direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<100>
Interrogation command
C_IC_NA_1
<101>
Counter interrogation command
C_CI_NA_1
<102>
Read command
C_RD_NA_1
<103>
Clock synchronization command
C_CS_NA_1
<104>
Test command
C_TS_NB_1
<105>
Reset process command
C_RP_NC_1
<106>
Delay acquisition command
C_DVD_NA_1
Parameter in control direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<110>
Parameter of measured value,
normalized value
P_ME_NA_1
<111>
Parameter of measured value, scaled
value
P_ME_NB_1
<112>
Parameter of measured value, short
floating point value
P_ME_NC_1
<113>
Parameter activation
P_AC_NA_1