User manual
Reference PTQ-104S Rev2 ♦ Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 160 of 195 ProSoft Technology, Inc.
February 22, 2013
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
400
2400
401
2401
402
2402
403
2403
...
...
409
2409
In order to send a change of deadband for M_ME_NA Point 400, the Client would
send a command type 110 to point 2400.
M_ME_NB
Monitored Measured Normalized Point
Associated Parameter Point
500
2500
501
2501
502
2502
503
2503
...
...
509
2509
In order to send a change of deadband for M_ME_NB Point 500, the Client would
send a command type 110 to point 2500.