User manual
PTQ-104S Rev2 ♦ Quantum Platform Reference
IEC 60870-5-104 Server for Quantum User Manual
ProSoft Technology, Inc. Page 145 of 195
February 22, 2013
Refer to the following parameter to configure the select/operate timeout period.
After the module receives the SELECT operation it will wait for this period of time
for the EXECUTE operation. If the module does not receive an EXECUTE
operation within this period of time it will require another SELECT operation
before the EXECUTE operation.
Command Points Addressing
Command points must be configured in a database area that is updated in the
module. You must associate each point to a database address in the PTQ-104S
module. The interpretation of the DB address parameter in the configuration
tables depends on the point type configured and the type of addressing
associated with that point type.
Data Type
Data Size
Addressing Type
C_SC_NA
1 bit
Bit
C_DC_NA
2 bits
Bit
C_RC_NA
1 byte
Byte
C_BO_NA
2 words
Double-word
C_SE_NA
1 word
Word
C_SE_NB
1 word
Word
C_SE_NC
2 words
Double-word