Operating instructions

PTQ-MCM Quantum / Unity Platform Configuring the Processor with Concept
Modbus Communication Module
Page 16 of 139 ProSoft Technology, Inc.
April 29, 2008
2.1 Information for Concept Version 2.6 Users
This guide uses Concept PLC Programming Software version 2.6 to configure
the Quantum PLC. The ProTalk installation CD includes MDC module
configuration files that help document the PTQ installation. Although not required,
these files should be installed before proceeding to the next section.
2.1.1 Installing MDC Configuration Files
1 From a PC with Concept 2.6 installed, choose Start / Programs / Concept /
ModConnect Tool.
This action opens the Concept Module Installation dialog box.
2 Choose File / Open Installation File.
This action opens the Open Installation File dialog box:
3 If you are using a Quantum processor, you will need the MDC files. In the
Open Installation File dialog box, navigate to the MDC Files directory on the
ProTalk CD.
4 Choose the MDC file and help file for your version of Concept:
o Concept 2.6 users: select PTQ_2_60.mdc and PTQMDC.hlp
o Concept 2.5 users: select PTQ_2_50.mdc and PTQMDC.hlp.
Select the files that go with the Concept version you are using, and then click
OK. This action opens the add New Modules dialog box.