User manual

Reference 49TPTQ-104C 48TQuantum Platform
12TUser Manual 47TIEC 60870-5-104 Client
Common Address of ASDU
(System-specific parameter)
One octet Two octets
Information object address
(System-specific parameter)
One octet Structured
Two octets Unstructured
Three octets
Cause of transmission
(System-specific parameter)
One octet Two octets (with originator address)
Length of APDU
(System-specific parameter, specify the maximum length of the APDU per
system)
The Maximum length of the APDU is 253 (default). The maximum length may be
reduced by the system.
Maximum length of 253 per APDU system
9.6.3 Selection of standard ASDUs
Process information in monitor direction
(Station-specific parameter; mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<1>
Single-point information
M_SP_NA_1
<2>
Single-point information with time tag
M_SP_TA_1
<3>
Double-point information
M_DP_NA_1
<4>
Double-point information with time tag
M_DP_TA_1
<5>
Step position information
M_ST_NA_1
<6>
Step position information with time tag
M_ST_TA_1
<7>
Bitstring of 32 bit
M_BO_NA_1
<8>
Bitstring of 32 bit with time tag
M_BO_TA_1
<9>
Measured value, normalized value
M_ME_NA_1
<10>
Measured value, normalized value with
time tag
M_ME_TA_1
<11>
Measured value, scaled value
M_ME_NB_1
<12>
Measured value, scaled value with time
tag
M_ME_TB_1
<13>
Measured value, short floating point
value
M_ME_NC_I
Page 120 of 136 ProSoft Technology, Inc.