User manual
1560-PDP
PROFIBUS – SCANport Adapter
23
E.4 : Adapter Output Image (Write to 1560-PDP)
Word
Name
Description
0
Diagnostics Control
Byte
When writing to a parameter
enter a value of (0x10h) This
will oneshot the parameter
value
1 Logic Control Word This word should be verified in
the A-B user manual for the
particular device being
controlled.
2 Reference Control This word should be verified in
the A-B user manual for the
particular device being
controlled.
3 Datalink - A1 Adapter I/O (*Number of
Datalinks set by DIP switch)
4 Datalink - A2 Adapter I/O (*Number of
Datalinks set by DIP switch)
5 Datalink - B1 Adapter I/O (*Number of
Datalinks set by DIP switch)
6 Datalink - B2 Adapter I/O (*Number of
Datalinks set by DIP switch)
7 Datalink - C1 Adapter I/O (*Number of
Datalinks set by DIP switch)
8 Datalink - C2 Adapter I/O (*Number of
Datalinks set by DIP switch)
9 Datalink - D1 Adapter I/O (*Number of
Datalinks set by DIP switch)
10 Datalink - D2 Adapter I/O (*Number of
Datalinks set by DIP switch)
11
Parameter Number
Write
Enter the value for the
parameter you wish to write
to(Parameter 112 = 112)
12 Parameter Value Enter the value to set the
parameter to
Writing A Parameter
1. Enter the parameter
number into word 11
2. Enter the parameter value
into word 12
3. Enter value 0x10h in word
0(This will oneshot the
value to the parameter)
4. Clear word 0