User manual
1560-PDP
PROFIBUS – SCANport Adapter
6
Dip Switches – SW1
8 7 6 5 4 3 2 1
Name
Description
X X X X X X X Node
Address
Selects the Profibus Node address
for this adapter. Binary weighting on
dip switches as follows:
Bit Value
0 1
1 2
2 4
3 8
4 16
5 32
6 64
Example:
6 5 4 3 2 1 0 Addr
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 2
0 0 0 0 0 1 1 3
- - - - - - - -
1 1 1 1 1 1 1 127
X Loss of
Comm
Failure
Enable
The action that the adapter will take
upon detecting loss of control from a
Siemens host. This action will not be
enabled until an initial Output
Command has been received from
the host, and the Timeout has
expired (See SW2 table below):
0 = Disable Failure
1 = Enable Failure
Dip Switches – SW2
8 7 6 5 4 3 2 1
Name
Description
X Byte Swap
(Default off)
Position is a function of the
Profibus host device
1 for Siemens S5
0 for all others
X X X Loss of Comm
Timeout Multiplier
The adapter has a default
timeout of 120ms. To adjust this
value, use the following positions:
Timeout
432 Value
000 120ms
001 120ms
010 240ms
011 360ms
100 480ms
101 600ms
110 720ms
111 840ms