560-PDP PROFIBUS ™ Adapter for Allen-Bradley SCANport Devices User Manual Rev 2 ProSoft Technology Inc. 5201 Truxtun Avenue, Third Floor Bakersfield, CA 93309 (661) 716-5100 (661) 716-5101 fax http://www.prosoft-technology.com E-mail: prosoft@prosoft-technology.
1560-PDP PROFIBUS – SCANport Adapter Please Read This Notice Successful application of the 1560-PDP card requires a reasonable working knowledge of the Allen-Bradley hardware to be interfaced with, and the application on which the combination is to be used.
1560-PDP PROFIBUS – SCANport Adapter Quick Start Guide In this section we have assembled a simple step-by-step procedure for installing and making the 1560-PDP unit operational. This discussion presumes that the application decision such as PROFIBUS addressing and hierarchy, SCANport cable length, etc. have been addressed prior to this point.
1560-PDP PROFIBUS – SCANport Adapter Table of Contents 1 2 Product Specifications ......................................................................................1 Mounting and SCANport Cabling Instructions........................................2 2.1 2.2 2.3 2.4 2.5 Mounting Instructions .......................................................................................2 Cable Requirements ........................................................................................
1560-PDP PROFIBUS – SCANport Adapter 1 Product Specifications The ProSoft Technology, Inc. 1560-PDP card is a hardware product designed to be a communications front end for Allen-Bradley SCANport compatible products (1336 Plus, 1336 Plus II, 1397, Force, Vector, 1305, SMC Dialogue Plus, SMP3, etc.
1560-PDP PROFIBUS – SCANport Adapter 2 Mounting and SCANport Cabling Instructions 2.1 Mounting Instructions Following are the mounting dimensions and layout drawings for the enclosed style communication module, such as the 1560-PDP. The following drawings are excerpted from A-B document 1203-5.5.
1560-PDP PROFIBUS – SCANport Adapter 2.2 Cable Requirements SCANport cables are available in either Male to Male or Male to Female configurations. Cables of up to 10 meters (33 feet) can be connected from the SCANport device to the 1560-PDP. If a Port Expander is used, the cable length from the master to the Port Expander must be subtracted from the cable length used to connect the device to the expander (B1 + C = max 10 meters).
1560-PDP PROFIBUS – SCANport Adapter 2.3 Hardware Setup The layout of the LEDs and the connectors on the 1560-PDP is shown in the diagram below. The power connections for 120/240VAC and the 24VDC are also shown.
1560-PDP PROFIBUS – SCANport Adapter 2.4 LED Indications NAME Profibus Status Color Green Red Status Steady Steady Blinking SCANport Status 2.5 Green Green Steady Blinking Red Steady Indication Profibus connection is in place with the host Profibus connection is not good. Check that the Profibus cable is connected to a host. Also, verify that the Profibus network is correctly terminated.
1560-PDP PROFIBUS – SCANport Adapter 8 Dip Switches – SW1 7 6 5 4 3 2 X X X X X X 1 X Name Node Address Description Selects the Profibus Node address for this adapter. Binary weighting on dip switches as follows: Bit 0 1 2 3 4 5 6 Value 1 2 4 8 16 32 64 Example: 6 0 0 0 1 X Loss of Comm Failure Enable 5 0 0 0 1 4 0 0 0 1 3 0 0 0 1 2 0 0 0 1 1 0 1 1 1 0 1 0 1 1 Addr 1 2 3 127 The action that the adapter will take upon detecting loss of control from a Siemens host.
1560-PDP PROFIBUS – SCANport Adapter (Continued) 8 X Dip Switches – SW2 7 6 5 4 3 2 X X X 1 Name Not Used Datalink Enable Description Determines how many datalink parameters to exchange between the drive and the 1560-PDP adapter: 87 00 01 10 11 7 Datalinks None A A& B A,B,C,D
1560-PDP PROFIBUS – SCANport Adapter 3 Adding 1560-PDP to Profibus Network Configuration The User must configure the Siemens Profibus Binary file using a Siemens compatible utility, importing the GSD file and configuring the I/O image as desired. A minimum configuration would normally include the Output Image (13 words) and the Input Image (11 words) The configuration shown below was developed using COM PROFIBUS version 3.3.
1560-PDP PROFIBUS – SCANport Adapter Step 3 : Select Configure Choose what adapter information you wish to access. A detailed description of the available options for configuring the adapter is available in the Appendix. See the Appendix for details on: Input IN/Datalinks – 11 words Adapter Out/Datalinks – 13 words Adapter Status – 10 words Parameter Values – 16 words The most common configuration is to select the Adapter In and Adapter Out options.
1560-PDP PROFIBUS – SCANport Adapter Step 5 : Assign I/O Addresses Choose what address will be associated with each data point, or let COM PROFIBUS decide by selecting Auto Address. Step 6 : Save the Profibus Configuration Save the PROFIBUS network configuration. Use this configuration along with your PLC programming software to setup control and monitoring of your AB drive.
60-PDP PROFIBUS – SCANport Adapter Appendix A : Device Specific Hints A.1 SMC Dialogue Plus The SMC Dialogue Plus does not support Datalinks, therefore the configuration of SW27 and 8 should not include any of the Datalinks Enabled. If a Datalink is enabled, the SCANport Status LED will toggle, indicating an error in the SCANport communications. The version of SMC which was tested (Rev 1.05) had 88 parameters. The 1560-PDP is able to read 32 of the parameters out of the SMP3 unit. A.
1560-PDP PROFIBUS – SCANport Adapter Logic Control Word Since the most common implementation of the 1560-PDP is with the variable speed drives, we have included the following table for the more commonly used control bits. This word should be verified in the A-B User Manual for the particular device being controlled.
1560-PDP PROFIBUS – SCANport Adapter Appendix B : SCANport Datalink Operation (Excerpted from A-B Publication 1203-5.2 - May 1995) In the following discussion, the term ‘Datalink’ is used extensively. When configuring some SCANport devices, the term ‘Adaptor I/O’ is used in place of Datalink. A Datalink is a type of pointer used by some SCANport devices to transfer information between a SCANport communication interface (such as the 1560-PDP) and a SCANport device (such as a VFD, SMP3, etc.).
1560-PDP PROFIBUS – SCANport Adapter Appendic C : Repair and Warranty Service and Repair The 1560-PDP card is an electronic product, designed and manufactured to function under somewhat adverse conditions. As with any product, through age, misapplication, or any one of many possible problems, the card may require repair. The 1560-PDP product has a one year parts and labor warranty according to the limits specified in the warranty.
1560-PDP PROFIBUS – SCANport Adapter Appendix D : PSFT087C.GSD File ;================================================================ ; GSD-file example for ProSoft Technology 1560-PDP Profibus Adapter ; Date: 09.19.98 ; Profibus DP Slave ; Language : English ; GSD Rev 2 Date: 02-24-99 ; 10-15-99 modified ;================================================================ #Profibus_DP ; ExtUserPrmData=1 "Number of PRM read" ; Unsigned8 0 0-32 EndExtUserPrmData ExtUserPrmData=2 "Drive Parameter No.
1560-PDP PROFIBUS – SCANport Adapter EndExtUserPrmData ExtUserPrmData=16 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=17 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=18 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=19 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=20 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=21 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=22 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=23 Unsigned8 0 0-255 EndExtUserPrmData ExtUserPrmData=24 Unsigne
1560-PDP PROFIBUS – SCANport Adapter Vendor_Name = "ProSoft Technology Inc" Model_Name = "1560-PDP SCANport Adapter" Revision = "Rev 1.0 - 1"; Ident_Number = 0x087C ; Need official ID from PTO Protocol_Ident = 0 ; 0 = Profibus DP Station_Type = 0 ; 0 = DP Slave FMS_supp = 0 ; No FMS support Hardware_Release = "01" ; Not a function of Hardware Release Software_Release = "1" ; Batch Number ; ; Supported Baud Rates 9.6_supp = 1 19.2_supp = 1 93.75_supp = 1 187.5_supp = 1 500_supp = 1 1.
1560-PDP PROFIBUS – SCANport Adapter Max_Input_Len = 106 ; ; ; ; ; 10 10 16 16 12 words words words words words + + 1 Diag Control Status Input Data Parameter Read Block Parameter Read Block 1 Diag Control Max_Output_Len = 26 Max_Data_Len = 132 ; Max_Diag_Data_Len = 10 ; ; Default Length of User Parameter User_Prm_Data_Len = 34 ; List of Parameters in Drive to read back ; ; First value is the number of parameters to read Max_User_Prm_Data_Len = 34 Ext_User_Prm_Data_Const(0)= 0x00,0x00,0x00,0x00,0x00,0
1560-PDP PROFIBUS – SCANport Adapter ; Unit_Diag_Bit(0) = "SCANport device not online" ; strings for diagnostics ; ; Definitions of physical slots ; ; Module Word Input Image ; Module = "Adptr In/Datalinks - 11 Words" 0x5A EndModule Module = "Adapter Status - 10 Words" 0x59 EndModule Module = "Parameter Values - 16 Words" 0x5F EndModule ; ; Module Word Output Image ; Module = "Adptr Out/Datalinks - 13 Words" 0x6C EndModule 19
1560-PDP PROFIBUS – SCANport Adapter Appendix E : Profibus Data Image Details E.1 : Adapter Input Image (Read from 1560-PDP) Word 0 1 Name Diagnostic Control Byte Status Word 2 Feedback Value 3 Datalink - A1 4 Datalink - A2 5 Datalink - B1 6 Datalink - B2 7 Datalink - C1 8 Datalink - C2 9 Datalink - D1 10 Datalink - D2 Description (Future) This word should be verified in the A-B user manual for the particular device being controlled.
1560-PDP PROFIBUS – SCANport Adapter E.2 : Adapter Status Image (Read from 1560-PDP) Word 0 Name SCANport Status Values Description 0 = Offline Indicates if 1560-PDP is logged 1 = Online into the drive.
1560-PDP PROFIBUS – SCANport Adapter E.
1560-PDP PROFIBUS – SCANport Adapter E.