User manual
MVI56-HART ♦ ControlLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 97 of 171
October 13, 2011
Parameter Value Config File Section
DB Address Status 3661
[HART PORT 1]
Auto-Poll DB Address 1200
Max Device Count 15
DB Address Status 3662
[HART PORT 2]
Auto-Poll DB Address 2000
Max Device Count 15
DB Address Status 3663
[HART PORT 3]
Auto-Poll DB Address 2800
Max Device Count 15
The HART database has the following structure.
The configuration file for this example shows that when the MAX Device Address
parameter is configured as 15, the module will reserve 750 words for each channel (15
devices x 50 words each) even though not all devices may be present on the network.