User manual

MVI56-HART ♦ ControlLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 93 of 171
October 13, 2011
DB Byte
Offset
Type Description Byte
Cnt
Data
Source
Use of Data
60 to 63 float Primary variable value 4 CMD 3 Status
64 to 67 float Secondary variable value 4 CMD 3 Status
68 to 71 float Tertiary variable value 4 CMD 3 Status
72 to 75 float Quaternary variable value 4 CMD 3 Status
76 to 79 float Upper transducer limit 4 CMD 14 Cfg
80 to 83 float Lower transducer limit 4 CMD 14 Cfg
84 to 87 float Minimum span 4 CMD 14 Cfg
88 to 91 float PV upper range value 4 CMD 15 Cfg
92 to 95 float PV lower range value 4 CMD 15 Cfg
96 to 99 float PV damping value (in seconds) 4 CMD 15 Cfg
TOTAL FLOAT BYTE COUNT 40
TOTAL FLOAT WORD COUNT 20
DB Regs/Device 50
Max DB Regs/channel for 15 Devices 750
Max DB Regs for HART Card 3000
The following table defines the auto-polling command status bits:
Bit # Description
0 Long Address Set (command 0 successful)
1 Command 13 successful (configuration)
2 Command 14 successful (configuration)
3 Command 15 successful (configuration)
4 Command 3 successful (data polling)
5 Reserved
6 Reserved
7 Reserved
The following topics describe the modes of module operation.
Auto-Poll Disabled Mode
If the auto-polling feature is disabled (Auto-Poll Code = N), the module functions as
shown in the following diagram:
Only the user commands are executed and all data is placed in and sourced from the
module's internal database. The user is responsible for constructing all commands to
control and monitor the instruments attached to the channel.